Your heat pump’s size is the heat the house loses on its design day, worked out one room at a time.

A dark heat pump on a slab beside a stone house with roses on the wall, and an air source heat pump at the far side of a stone house garden

Key Takeaways

A dark heat pump on a slab beside a stone house with hills behind, and a white heat pump on a path beside a brick house and its garden
  • Heat pump size is the heat loss of your house at its outdoor design temperature, worked out room by room.
  • On grant jobs paid from April to June 2026, the median air source heat pump was 8 kW, and the middle half ran from 6 kW to 10.8 kW. Your house can land anywhere in that range or outside it.
  • The MCS design standard asks for a unit that covers 100% of the calculated heat load at the design flow temperature, without help from an electric heater.
  • Default wall figures can be wrong in both directions. Measured solid walls in a BRE study lost a quarter to two-fifths less heat than the assumed value, and insulated cavity walls lost more.
  • Height above sea level lowers your design temperature. On the MCS calculator’s rule, a house at about 300 m, the height of Buxton, gets a design temperature 1.2°C colder than Woodford, the Manchester reference station.
  • The hot water cylinder has its own sum: 45 litres a day for each person, counting at least one more person than you have bedrooms.
In This Guide

In the Energy Saving Trust’s heat pump field trial, analysed for the government, one three-bedroom detached house with pre-1900 solid walls had a 12 kW ground source heat pump. A heat loss calculation to the MCS design standard of the day put the right size at 9.4 kW, so the house had 28% more heat pump than its heat loss called for. For the trial’s second phase the maker swapped in an 8 kW unit, which the same report judged too small (DECC, May 2013). The sizing rules below apply to air source and ground source units alike.

The size you need is the heat your house loses, in kilowatts, at the coldest outdoor temperature it is designed for. A surveyor works that out room by room, and floor area, bedroom count and the size of your old boiler count as far as they change the heat loss, and no further.

Heat Pump Size Chart: The kW Figures On Real Jobs

A stone house with a white heat pump against its side wall, and a white heat pump on a slab at the corner of a brick house

The government publishes the median and quartile sizes of the air source heat pumps paid for through the Boiler Upgrade Scheme in England and Wales. The figures below come from its August 2026 release and count jobs by the quarter the grant was paid.

Quarter grants were paidLower quartileMedianUpper quartile
April to June 20228 kW10 kW12 kW
April to June 20266 kW8 kW10.8 kW

What the 2026 figures show

A quarter of the 2026 jobs used a unit of 6 kW or less, and a quarter used one bigger than 10.8 kW. Over four years the median fell from 10 kW to 8 kW. DESNZ gives no reason for the fall, so read it as a record of what installers fitted.

Same street, different sizes

Treat the chart as a range of real answers. A 6 kW house and an 11 kW house can sit on the same street, with the same number of bedrooms.

The conditions behind a kW figure

The kW figure on a heat pump also needs its conditions beside it. A unit puts out less heat on a frosty day than on a mild one, and less when it has to make hotter water. The MCS standard tells the designer to pick a unit on its output at your flow temperature, so two models sold as “8 kW” can cover different houses.

The Heat Loss Survey That Sizes A Heat Pump

A thermal imaging camera checking the wall of a dining room, a sitting room with an old radiator taken off the wall and dust sheets down and an air source heat pump beside the door of a stone cottage with a vegetable garden

MCS publishes the heat pump design standard, MIS 3005-D. Issue 3.0 is dated 5 December 2025, and installers certified by MCS have had to work to it from that day. Its space heating section sets out the steps in order.

  1. Room by room, at set indoor temperatures

    The designer calculates the heat each room loses through its walls, windows, floor and ceiling, and through air leaking in and out. The calculation follows the European method, BS EN 12831-1:2017. Each room gets a target temperature from the standard’s Table 1, taken from CIBSE guidance: 21°C for living and dining rooms, 18°C for bedrooms, halls and kitchens, and 22°C for bathrooms.

  2. The outdoor design temperature

    Table 2 of the standard gives outdoor design temperatures from CIBSE Guide A. For Manchester, at 75 m above sea level, the outdoor air sits at or above -2.7°C for 99% of the hours in a year and at or above -4.5°C for 99.6% of them. The designer picks a column for your location, and a design on the colder 99.6% figure needs no extra allowance for heating that runs in bursts.

    The MCS Heat Load Calculator takes the nearest of 14 weather stations and lowers the temperature by 0.6°C for each whole 100 m your home sits above that station. For an SK postcode the nearest station is Woodford, near Stockport, at 88 m and -4.5°C, the same 99.6% figure as the standard’s Manchester row, and the calculator counts your height from Woodford’s 88 m.

  3. The floor under you

    A solid floor on the ground loses heat to the earth, and the earth stays near the yearly average air temperature. The standard uses that average for solid floors, which the MCS calculator puts at 10.0°C for the West Pennines (Ringway). A suspended timber floor with air below it uses the full outdoor design temperature, so the same room loses more through a suspended floor.

  4. Matching the unit to the total

    The room figures add up to the heat load of the house. For a heat pump that heats the house on its own, the standard says the chosen unit must cover at least 100% of that load at the design flow temperature, with no help from a supplementary electric heater, and keep the rooms at temperature through its defrost cycles. For a hybrid system that keeps a boiler, the heat pump has to cover at least 55% of the load at 55°C flow.

MCS also publishes MCS 031, the performance estimate your installer gives you at the quoting stage. MCS states that the tool does not size a heat pump. Sizing comes from the heat load above.

Watts Per Square Metre And Bedroom Counts Mislead

A white heat pump on a lawn against a sandstone house, and a heat pump on a block paved drive beside a timber fence

A rule of thumb gives every square metre of floor the same number of watts. A heat pump size calculator online often starts from floor area and bedroom count too. Both put a 100 m² stone end-of-terrace and a 100 m² semi with filled cavities in the same box, and the heat loss of those two houses can sit kilowatts apart.

The walls show the gap. BRE measured the heat flowing through the walls of real English homes for the government, and compared it with the values the EPC method assumed at the time (BRE for DECC, July 2014):

Wall typeHomes measuredMean measured U-value (W/m²K)Value the EPC method assumed (W/m²K)
Solid walls of stone, concrete or thick brick331.282.1
Solid brick walls under 330 mm851.572.1
Insulated cavity walls1090.670.5

A U-value is the watts that pass through one square metre of wall for each degree of difference between inside and out. Lower is better.

Worked example one: the same wall, assumed and measured

These figures illustrate the method and describe no real house. Take 80 m² of outside wall and a 25.5°C difference between a 21°C room and a -4.5°C design day:

  • Stone wall at the assumed 2.1: 80 × 2.1 × 25.5 = about 4.3 kW through the walls.
  • Stone wall at the measured mean of 1.28: 80 × 1.28 × 25.5 = about 2.6 kW.
  • Insulated cavity at the assumed 0.5: about 1.0 kW.
  • Insulated cavity at the measured mean of 0.67: about 1.4 kW.

On the stone house, the assumed figure adds about 1.7 kW from the walls alone, which can push the unit up a size. On the cavity house the assumption runs the other way and leaves about 0.35 kW out. BRE went back to cavity walls first logged as unfilled and found insulation in nine of ten, of variable quality and density, which BRE said helps explain the wide spread of results in that group. A surveyor who checks your wall thickness and what it is built from will get nearer your real figure than any default.

Both Walls On One Scale

Heat lost through 80 m² of outside wall with the room at 21°C on a -4.5°C design day. The stone default sits above the measured figure and the cavity default sits below it.

Stone, value the EPC method assumed (U-value 2.1)

about 4.3 kW

Stone, BRE measured mean (U-value 1.28)

about 2.6 kW

Insulated cavity, value assumed (U-value 0.5)

about 1.0 kW

Insulated cavity, BRE measured mean (U-value 0.67)

about 1.4 kW

Our arithmetic, for illustration, on BRE measurements for DECC (July 2014). The figures describe no real house.

Worked Example Two: One House At Three Heights

An air source heat pump beside a timber and glass garden room on a stone house, and a white heat pump on a slab in the yard of a brick terrace

New Mills shows why height counts. The parish runs from about 120 m above sea level at its lowest point to 370 m above Rowarth. Buxton sits at about 300 m. Using the MCS calculator’s rule from Woodford (88 m, -4.5°C):

House positionHeight above WoodfordDesign temperatureHeat load of the example house
Valley floor, about 120 munder 100 m-4.5°C6.0 kW
Valley side, 200 mone whole 100 m-5.1°Cabout 6.1 kW
About 300 m, the height of Buxtontwo whole 100 m-5.7°Cabout 6.3 kW

Our arithmetic, for illustration: a house that loses 6.0 kW at -4.5°C with a single indoor figure of 21°C loses about 235 W for each degree of difference, so each colder design temperature adds that much per degree. A real design uses each room’s own target temperature.

The hill adds about 5% here. Your walls, windows and loft move the answer further, which is why a survey measures those first. Height still matters at the margin, where 0.3 kW can decide between two sizes of unit.

Pick A Height For The Example House

The example house loses 6.0 kW at -4.5°C. Pick a height for it. The MCS calculator takes 0.6°C off the design temperature for each whole 100 m the house sits above the Woodford weather station, which is at 88 m.

Where the house sits

Height above Woodford

Under 100 m

Design temperature

-4.5°C

Heat load of the example house

6.0 kW

The valley floor sits under 100 m above Woodford, so the house keeps the station’s -4.5°C.

Our arithmetic, for illustration: about 235 W for each degree of difference, with one indoor figure of 21°C. A real design uses each room’s own target temperature.

Too Big Or Too Small: What Each One Costs You

A red brick house with a white heat pump beside the patio and garden, and a dark heat pump on a slab in the side passage of a brick house

A unit that is too big

Each heat pump has a lowest output it can run at, set by its maker. Once the house needs less heat than that, the unit switches off and on. Take the 6 kW example house on a 5°C day: it needs about 3.8 kW, a little over a third of the rated output of a 10.8 kW unit. The field trial report notes that laboratory tests showed performance can drop by a large margin when a heat pump runs in on-off cycles shorter than six minutes. The bigger unit also costs more to buy.

The trial’s own analysis found a small drop in space heating efficiency on ground source sites with small heat demands, and suggested oversizing as a possible cause, while saying more work was needed to confirm it.

The 6 kW Example House Against A 10.8 kW Unit

Heat the house needs on a 5°C day

about 3.8 kW

Heat load on the -4.5°C design day

6.0 kW

Rated output of the bigger unit

10.8 kW

Our arithmetic, for illustration: about 235 W for each degree between 21°C inside and 5°C outside comes to about 3.8 kW, a little over a third of the bigger unit’s rated 10.8 kW.

A unit that is too small

The MCS standard asks for 100% of the heat load from the heat pump, so the electric heater inside many units stays out of the sums. An undersized unit falls short on the coldest days, and the electric heater or a cold room makes up the gap. An electric heater gives about one unit of heat for each unit of electricity, while our designs aim for 3.5 to 4.0 units of heat from the heat pump where the house allows it. Our heat pump costs guide works through what those units cost on today’s price cap.

A Heat Pump’s kW Rating Depends On The Water It Makes

A new column radiator in a bright empty room with dust sheets down, and a white heat pump on a slab against a red brick side wall

Flow temperature, defined

Design flow temperature is the temperature of the water leaving the heat pump on the design day. The heat pump’s output at that temperature is the figure the standard sizes against, and the radiators have to give out each room’s heat at that temperature too.

Designs above 55°C

The MCS standard steers designs to 55°C or below. It says to avoid high temperature heat pumps unless the job needs water hotter than 55°C, and where a design proposes more than 55°C, the installer should also give you a design at 55°C or below, and has to explain the difference in efficiency and energy use so you can choose. Listed buildings and rooms with no space for a bigger radiator are the cases the standard names.

The radiator trade-off

A lower flow temperature lets the heat pump work less hard for each unit of heat, and it asks more of the radiators. The radiator side of that trade, room by room, is in our guide to heat pump radiators.

Sizing The Hot Water Cylinder

A white heat pump on a slab beside a rendered house with hills behind, and a dark heat pump on wall brackets below a window on a brick house

A heat pump makes hot water in batches and stores it, so the cylinder needs a size of its own, and the MCS standard starts that sum from your household. Daily hot water demand is 45 litres times N, where N is the greater of your bedroom count plus one or the number of people who live there:

BedroomsPeople counted (at least)Daily hot water demand (the starting figure for the cylinder)
23135 litres
34180 litres
45225 litres
56270 litres

A three-bedroom house with five people in it counts five, so 225 litres a day.

Work Out Your Daily Hot Water Figure

Pick your bedrooms and the number of people at home. The MCS standard counts the greater of your bedrooms plus one or your household, and allows 45 litres a day for each person.

Bedrooms

People who live there

People counted

4 people

Your bedrooms plus one

Daily hot water demand

180 litres a day

45 × 4

The designer picks a cylinder from that daily figure and the heat pump’s output, and agrees the reheat time with you. The coil inside needs more surface than a boiler cylinder because the water reaching it runs cooler, and a cylinder labelled to the Hot Water Association’s heat pump specification, HWA 002:2020, meets that part of the standard. The heat pump also has to reach at least 55°C flow on the design day. An existing cylinder can stay if its insulation, its condition and its size pass the standard’s checks.

If you run a combi now, the cylinder needs a new home in the house, and the standard accepts that the space you can spare may cap its size. Our guide to a heat pump or a combi boiler covers that choice. If solar panels are on your list as well, the solar sizing guide adds the electricity a heat pump brings.

Heat Pump Sizing Across The High Peak, Stockport And Manchester

A white heat pump on frosty ground beside a stone cottage, and a heat pump in the small back yard of a stone terrace

Our heat pump surveys take in Stockport and Manchester, Glossop, Marple, Whaley Bridge and Buxton across the High Peak, and the Hope Valley, and they carry on to Sheffield, Chesterfield and Matlock. Two things in that patch move the sums above: how old the houses are and how high they sit.

Older homes and solid walls

In the High Peak, about three in ten homes on the Council Tax list were built before 1900, against about one in seven across England (VOA, 31 March 2026). The 2021 Census counted 33% of High Peak homes as terraced, against 23% across England. Older solid walls and end-of-terrace gables are where default wall values miss, in either direction, and a measured figure keeps the unit at the size the house needs.

Valley floor to Buxton

Height adds its own step. A house on the valley floor in New Mills and one at Buxton’s height sit about 180 m apart, and the design temperature moves 0.6°C with each whole 100 m above Woodford. Our pages on heat pumps in the High Peak, heat pumps in Buxton and heat pump installation in Manchester cover each area.

Sizing Your Heat Pump With First Point

A black heat pump on a wall bracket on a sandstone wall, seen from below, and a First Point engineer feeding a coil of pipe through scaffolding on a building site

You see the heat loss and the unit size on paper before anyone talks about a model.

What You Get

  • The survey measures what the sums above need. Our lead engineer measures your house room by room: the walls, windows and floors each heat loss figure depends on.
  • The design names a size and the conditions behind it. The unit, the emitters, the pipework and the flow rates, sized to a target SCOP of 3.5 to 4.0 where the house allows it, with the figure your design reaches written into your quote.
  • The quote is fixed. The price you sign is the price you pay, and the running-cost workings come with it for you to check against any other installer’s.
  • Commissioning proves the design. One week to one month on site, depending on the house and the system, then we set the flow temperatures and test them against the design numbers.
  • Two years of workmanship cover on our installation, alongside the manufacturer’s warranty.

If the numbers don’t add up for your house, we say so at the survey, before any money changes hands. The heat pump installation page walks through each step from survey to handover.

Heat Pump Sizing Questions

A close view of a heat pump on its feet on a gravel base, and a dark heat pump on a gravel strip against a red brick wall

What size heat pump do I need for a 3 bedroom house?

Your heat loss decides it. The median air source heat pump on grant jobs paid from April to June 2026 was 8 kW, with the middle half between 6 kW and 10.8 kW, and three-bedroom houses sit across that whole range. A filled-cavity semi can need far less than a stone end-of-terrace with the same rooms.

How many kW heat pump do I need for a 4 bed house?

A four-bedroom house often loses more heat than a three-bedroom one, and the survey still gives the number. Ask for the room-by-room heat load at your design temperature, and check that the unit covers 100% of it at the design flow temperature, with no electric heater in the sum.

Can I use a heat pump size calculator?

An online calculator built on floor area or bedrooms gives you a starting range. It can’t see your wall thickness, your floor or your height above sea level. MCS runs its own Heat Load Calculator for installers, built on BS EN 12831-1, and a measured survey supplies the figures a calculator like that needs.

Is it bad to oversize a heat pump?

An oversized unit costs more to buy and runs in short on-off bursts on mild days. The government’s field trial report notes that laboratory tests showed performance can drop by a large margin when a heat pump runs in on-off cycles shorter than six minutes.

What size hot water tank do I need with a heat pump?

The MCS standard starts from 45 litres a day for each person, counting at least your bedrooms plus one. A three-bedroom house comes to 180 litres a day. The cylinder volume then follows from that demand, the heat pump’s output and the reheat time you agree with your designer.

Does a heat pump need a buffer tank?

Sometimes, and the water in your heating circuit decides. Every heat pump needs a minimum volume of water it can always circulate, above all to melt the ice off its coil in a defrost, and the installation manual for each model sets that figure. Radiators that stay open, with no valve able to shut them all, can hold enough on their own. If zone valves or thermostatic valves could close most of the circuit, the design adds the missing volume, often with a buffer tank. A buffer is one more insulated tank to find room for, separate from the hot water cylinder sized above, so our design puts one in where the water sums call for it and nowhere else.

Do you size heat pumps for homes in Glossop, Buxton and Stockport?

We do. On the MCS calculator’s height rule, a house at Buxton’s height starts 1.2°C colder than one at Stockport’s level, before we measure a single room.

Lewis Harding, head plumber and gas engineer at First Point Plumbing and Heating, smiling in a black company hoodie

Lewis Harding

Head Plumber and Gas Engineer

Lewis has ten years in the trade. He started on his own, fitting boilers and bathrooms, and has spent the past year on heat pump and system design.

  • Gas Safe 930763
  • F-Gas FGAS3028681
  • Which? Trusted Trader
About Lewis And The Team

Sources

A floor plan and a printed room schedule on a wooden table beside a mug and reading glasses, and a white heat pump on a slab in the paved side passage of a brick house
  1. DESNZ, Boiler Upgrade Scheme statistics: August 2026 (published 24 September 2026), Table Q1.1A median and quartile capacity of air-to-water heat pumps by quarter of redemption, England and Wales
  2. MCS, MIS 3005-D The Heat Pump Standard (Design), Issue 3.0, dated 5 December 2025, mandatory from 5 December 2025: clauses 5.5.1, 5.5.2, 5.5.4, 5.5.5, 5.6.2 to 5.6.7, Tables 1 and 2
  3. MCS Heat Load Calculator, Design Conditions (CIBSE Guide A 2015 Table 2.5 stations, altitude rule, MGD 007 annual mean temperatures)
  4. MCS, An installer guide to the updated heat pump performance estimate standard and tool, MCS 031 (19 February 2025)
  5. BRE for DECC, In-situ measurements of wall U-values in English housing (4 July 2014), Table 1
  6. DECC, Kiwa Gastec, EA Technology, Detailed analysis from the second phase of the Energy Saving Trust’s heat pump field trial (May 2013), sections 3.6.4, 4.3 (site 419) and 8.2.7
  7. ONS, Census 2021, TS044 Accommodation type, High Peak and England (via Nomis)
  8. VOA, Council Tax: stock of properties 2026, Table CTSOP4.0 build period by area at 31 March 2026 (published 24 September 2026)
  9. Wikipedia, New Mills (parish height range) and Buxton (height of the town)

Google Reviews From Our Customers

Three First Point engineers in company hoodies in front of the liveried van, a First Point engineer on a ladder in a narrow gap between two stone walls and a dark heat pump on a concrete base against a red brick wall with lavender beside it

More Guides

All Guides

Get Your Heat Pump Sized From Your Own House

Four First Point engineers in black branded polos standing in a row in front of a dark grey crew van

Book the free design survey and our lead engineer measures your house room by room. The written design gives you the heat loss, the unit size, the flow temperature and the radiators that grow, with a fixed price beside it.