Are Heat Pumps Noisy? Siting And Planning In The High Peak, Greater Manchester, Sheffield And Leeds

You may hear one in a cold spell or a defrost, and doubling its distance from next door’s window takes about 6 dB off.

A Stiebel Eltron air source heat pump fitted by First Point on a galvanised bracket on a stone wall, and four First Point engineers in front of their van in the sun, for High Peak heat pump noise and siting

Key Takeaways

An air source heat pump on a raised base beside a stone gable, and a red brick house with a white heat pump beside the patio, illustrating heat pump noise, siting and planning
  • MCS 020 a) separates the sound power a unit makes from the sound pressure that reaches next door.
  • In the standard’s own example a 60 dB(A) unit 8 metres from a bedroom window comes out at 32.0 dB(A) there.
  • A solid wall that hides the whole window takes 10 dB off, and hedges or trellis take nothing.
  • The one-metre boundary rule went in May 2025, so a unit by the fence can be permitted development if it passes the sound calculation.
  • Detached houses can have two units under permitted development, and other houses one.
In This Guide

Are heat pumps noisy enough to bother next door? In England the test happens at a spot one metre outside your neighbour’s bedroom or living room window. The standard the planning rules point to, MCS 020 a), sets a limit of 37 dB(A) at that spot, and the installer works the level out on paper before the unit goes on the wall. The version in force is Issue 1.1, dated 14 April 2025.

If the calculation passes and the unit meets the other permitted development conditions, you need no planning application. If it fails, you have four routes: move the unit, add a solid barrier, pick a model with a lower sound rating, or apply for planning permission. We run that check for the exact spot on your house before anything is fixed, on jobs across the High Peak, Greater Manchester, Sheffield and Leeds.

Heat Pump Noise In Numbers

A Stiebel Eltron heat pump beside the back door of a stone farmhouse well away from any boundary, and Lewis Harding of First Point on a building site, for a Whaley Bridge heat pump noise check

Two Figures, One Worked Example

  • Heat pump advice mixes up two decibel figures. The sound power level is the noise the unit makes at source, printed on its energy label and product sheet.
  • The sound pressure level is what reaches a particular spot, such as that window next door, after distance, walls and fences have taken their share. MCS 020 a) turns the first into the second.
  • Its own worked example takes a unit with a sound power of 60 dB(A), on the ground against one wall, 8 metres from a neighbour’s first-floor bedroom window, with a brick wall in between that hides part of the view.

Level At The Window In The Example

The answer comes out at 32.0 dB(A), 5 dB under the limit (MCS 020 a), Appendix A).

Two rules in the standard carry most weight:

  • The installer has to use the unit’s normal sound power figure. The quieter “low noise mode” figure is not allowed in the calculation
  • Every neighbouring habitable room window or door that could hear the unit counts, on all sides, because the closest one is not always the loudest

Older guides quote 42 dB(A), a figure from the previous MCS 020, which added an assumed background noise level to the sum (MCS 020 consultation response, November 2024). If a neighbour has read one of those, the test that counts is 37 dB(A) at their window with the unit’s full rating, and you can ask to see that working before you agree a spot.

The Times You Might Hear It

A close view of a heat pump on its feet on a gravel base, and an air source heat pump beside a timber clad extension with hills behind, illustrating the times you might hear a heat pump

A unit that passes the calculation can still be audible at times. MCS’s installer guidance lists them: cold spells when the unit works harder, while it heats your hot water, during a defrost cycle, and when it needs maintenance or has a fault (MCS, Installation Guidance for Mitigating Noise from Air Source Heat Pumps, V1, September 2025).

That gives you a few practical controls:

Practical Controls

  • Schedule hot water heating outside the hours people sleep
  • Use quiet or eco modes for occasional hours, knowing they can cut heat output and efficiency
  • Keep the fan clear and the fixings tight, since MCS links a noisier unit to a blocked fan or loose parts; a yearly heat pump service cleans the coils and filters

MCS also advises telling the neighbours what to expect before the unit arrives. A word over the fence before install day costs nothing, and a well-sited unit gives them less to notice in the first place.

Siting: Where The Unit Goes

An air source heat pump on a base at the corner of a brick and stone house, and galvanised wall brackets and pipe tails ready for a heat pump on a stone wall, illustrating where the unit goes

Distance

In the standard’s formula, doubling the distance to a window takes about 6 dB off the result. Moving a unit from 4 metres to 8 metres from the nearest window next door takes off a little more than a solid wall that hides part of the view, which counts for 5 dB.

Reflecting Surfaces

Sound bounces off hard surfaces within a metre of the unit, and each one raises the level at the neighbour’s window. MCS 020 a) counts the ground and walls but not plants. A unit on the ground against one wall has two reflecting surfaces; tucked into a corner it has three. A unit boxed in by more than three, such as one in a small lightwell, fails the standard outright.

A Stiebel Eltron heat pump on a slab beside the patio of a cream rendered house and another behind a tall dry stone wall that screens it from next door, for Furness Vale homes

Barriers

Masonry Wall Or Thick Solid Fence

A brick or masonry wall, or a solid fence at least 18 mm thick with no gaps, extending a metre or more past each side of the unit, takes 10 dB off when it blocks all view of the window and 5 dB when it hides part of it.

Thinner Solid Fence

A thinner solid fence takes 5 dB or 2.5 dB. Hedges, trellis and gappy fences count for nothing, however thick they look.

Facing And Fixings

MCS’s guidance says to face the unit away from neighbouring homes and your own habitable rooms where you can, and to avoid enclosed corners. Anti-vibration feet and flexible hose connections cut the hum travelling into the wall.

We keep the unit away from bedrooms, with siting checked against the sound calculation and the planning rules inside the design, before we promise anything. The standard asks the installer to keep one copy of the completed sound calculation and give you another, so ask for yours, whoever fits your system.

Terraces, Semis And Small Yards From Glossop To Leeds

A heat pump in the small back yard of a stone terrace, and a heat pump on the flagged yard of a brick terrace beside the bins, illustrating terraces, semis and small yards

The sums above give different answers street by street, and the type of house decides which of them bites.

Stone Terraces With Walled Yards

In Glossop, New Mills and Whaley Bridge many terraces have a small back yard with stone walls on two or three sides. Each wall within a metre of the unit counts as a reflecting surface, so a unit pushed into the corner of the yard scores worse than the same unit set out from the walls.

Semis With A Side Passage

On a semi in Stockport, Marple or south Manchester, the side passage looks like the tidy spot. It puts the unit between two walls and close to next door’s side windows, so the back garden often passes the calculation where the passage fails.

Back-To-Backs And City Terraces

A back-to-back in Leeds or a terrace in Sheffield with no yard can leave the front wall as the only option. That works at ground-floor level outside a conservation area, but inside one a wall facing the road is ruled out, and the job needs a planning application.

Detached Houses With Room To Spare

Out on the edge of Hayfield or Chinley, distance does most of the work: a detached house has room to put the unit well away from any neighbour’s window, and it can take two units under permitted development.

At the survey our lead engineer tries each possible spot against the sum, so you see the trade-off between the neat spot and the quiet one before the design is fixed.

Space Around The Unit

An air source heat pump on a concrete plinth against a stone wall, and insulated heat pump pipes running into a stone wall, illustrating the clear space around the unit

The clear air the unit needs around it comes from the manufacturer’s manual for the exact model, so the space around a possible spot is part of the survey.

The old rule that kept a unit at least a metre from the boundary went in May 2025. A unit near the fence line can now be permitted development if it passes the sound calculation, and a solid boundary wall can count as a barrier in that sum. On a narrow plot that opens up spots the old rule shut, and we check them against the clearances your model needs.

Heat Pump Covers And Acoustic Enclosures: What They Fix And What They Cost You

A heat pump cover promises a tidier garden and a quieter unit, and the right one can deliver both. Build the box the wrong way and the unit pays for its new look in electricity, because it can’t breathe.

The outdoor unit pulls air across its coil and throws it out through the fan, and the clearances in the section above exist to keep that air moving. A box is the quickest way to eat into them.

A Box That Costs You Heat

  • The air leaving the fan comes out colder than the air around it. Close the unit in and it breathes that chilled air again, the coil runs colder, frost builds sooner and the unit spends longer in defrost instead of heating your house. The Institute of Acoustics warns that an enclosure can affect a heat pump’s heat output.
  • A winter cover over a running unit blocks the air it works with. The unit is built to sit outdoors all year, so it stays uncovered while it runs.
  • Some newer units run on propane (R290), and their manuals set rules on what may sit close to the unit so that gas from a leak can disperse. Check any enclosure against the manual for your model before it goes up.

A Screen That Earns Its Place

A slatted screen that stands off the unit, open above it and in front of the fan, can hide it from the garden or the road while keeping the clearances. Two limits apply before you buy one:

  • Size: permitted development caps an outdoor unit on a house at 1.5 cubic metres, and the law counts “any housing” inside that volume. A bulky enclosure can push a unit that passed over the limit.
  • Sound: acoustic enclosures do cut noise, but the Institute of Acoustics says they are not always as effective as claimed. If you want one counted in the MCS 020 a) sound calculation, ask its maker for a tested sound figure for your model inside it, and check the clearances still hold. A solid wall or fence of the kind described under Barriers above takes up to 10 dB off without touching the unit.

Our lead engineer lets distance and a solid barrier do the noise work at the survey, before anyone talks about a box. If you still want a screen for looks, the design checks it against your model’s clearances and the planning volume before it goes up.

Planning Permission: The Rules In England Since May 2025

A stone house with solar panels on its roof and a heat pump by the wall, and a stone house with a white heat pump at the side of a wide lawn, illustrating permitted development rules for heat pumps

New permitted development rules for air source heat pumps came into force in England on 29 May 2025 (SI 2025/560, amending GPDO Schedule 2, Part 14, Class G). A heat pump on a house needs no planning application if it meets these conditions:

  • Up to two units on a detached house, and one on any other house or block of flats
  • An outdoor unit no larger than 1.5 cubic metres on a house, or 0.6 cubic metres on flats
  • The unit passes the MCS 020 a) sound calculation
  • It does not sit on a pitched roof, or within a metre of the edge of a flat roof
  • Outside conservation areas and World Heritage Sites, it does not go on a wall that fronts a highway above ground-floor level
  • It is not used solely for cooling

The unit also has to be sited to limit its effect on the look of the building and the area, and removed once it is no longer needed. Listed buildings and scheduled monuments fall outside these rules, so a listed home needs a planning application and, where the work affects its character, listed building consent.

Conservation Areas And The National Park

Ruled Out In A Conservation Area

Inside a conservation area, the unit cannot go on a wall or roof that fronts a highway, or anywhere nearer to a highway than the part of the house closest to it.

Where That Points The Unit

In practice that points the unit to the back of the house or a side wall away from the road.

The Peak District National Park Authority lists air source heat pumps among the devices that may not need planning permission, and asks owners of listed buildings or homes in conservation areas to contact it first (PDNPA, Planning questions and answers). The park boundary runs through the High Peak, so two addresses a mile apart can sit under different authorities: the National Park Authority inside it, High Peak Borough Council outside. A council can also remove permitted development rights for an area with an Article 4 direction, and a lawful development certificate gives a binding answer when the position is unclear (GOV.UK, When is permission required?).

Councils Beyond The High Peak

Each Greater Manchester borough decides for its own homes, Stockport, Tameside and Manchester among them, and Sheffield City Council and Leeds City Council decide in those cities, each with its own conservation areas and any Article 4 directions. For a house in Chinley, Marple or Crookes, we check the authority and any conservation area before the design fixes a position, so you don’t find out after the unit is on the wall.

If A Neighbour Complains About The Noise

A heat pump on a block paved drive beside a timber fence, and a white heat pump on a path beside a brick house and its garden, illustrating what happens if a neighbour complains

A council has to look into a complaint about noise that may be a statutory nuisance, meaning noise that interferes unreasonably and substantially with the use of a home. If the council finds one, it serves an abatement notice that makes whoever is responsible stop or restrict the noise (GOV.UK, Noise nuisances: how councils deal with complaints). Before it gets that far, four steps help:

Four Steps If A Neighbour Raises It

  • Talk to the neighbour, and find out when they hear it and from which room
  • Show them the completed MCS 020 a) sound calculation for the spot
  • Note the times and the weather, since a defrost or a cold spell explains a lot
  • Book a service visit if the sound has changed, which points to a fault more than to the siting

If a fixing we fitted has worked loose, our two-year workmanship guarantee covers putting it right, and our Heat Pump Care Plans put you ahead of non-plan customers for a visit, where availability allows. If running costs are your other worry, our heat pump costs guide works through the install price and the bills.

The fixed quote that follows also sets out what the system will cost to run, and our heat pump installation page has the full install process.

Questions About Neighbours, Boundaries And Quiet Mode

A white heat pump on a slab behind a dry stone wall with lavender, and a white heat pump on a slab at the corner of a brick house, illustrating questions about neighbours, boundaries and quiet mode

Will my neighbours in a High Peak terrace hear the heat pump?

They may hear it at times, most likely in cold weather, during a defrost or while it heats hot water. For permitted development, the calculated level at their nearest window has to come out at 37 dB(A) or lower, using the unit’s full sound rating.

Can a heat pump go next to the boundary fence in Stockport or Manchester?

Yes, in England since 29 May 2025. The one-metre rule no longer applies, but the unit still has to pass the sound calculation, and a neighbour’s window close to the fence makes that harder.

Can I have two heat pumps on a detached house in Hayfield or Chinley?

Yes. MCS 020 a) has a separate calculation that adds the two units’ sound together at each window, so the pair has to pass as a pair.

Does quiet mode get a heat pump through the noise rules in Sheffield or Leeds?

No. The calculation uses the unit’s normal sound power, so the siting has to pass without quiet mode.

Do I need planning permission for a heat pump in the Peak District National Park?

Often not, if the unit meets the permitted development conditions above. The National Park Authority asks owners of listed buildings and homes in conservation areas to contact it first, and we check which authority covers your address at the survey.

Lewis Harding, head plumber and gas engineer at First Point Plumbing and Heating, smiling in a black company hoodie

Lewis Harding

Head Plumber and Gas Engineer

Lewis has ten years in the trade. He started on his own, fitting boilers and bathrooms, and has spent the past year on heat pump and system design.

  • Gas Safe 930763
  • F-Gas FGAS3028681
  • Which? Trusted Trader
About Lewis And The Team

Sources

A hand setting a heat pump controller on a hallway wall, illustrating the sources behind this guide
  1. MCS 020 a), Appendix A
  2. MCS 020 consultation response, November 2024
  3. MCS, Installation Guidance for Mitigating Noise from Air Source Heat Pumps, V1, September 2025
  4. SI 2025/560, amending GPDO Schedule 2, Part 14, Class G
  5. PDNPA, Planning questions and answers
  6. GOV.UK, When is permission required?
  7. GOV.UK, Noise nuisances: how councils deal with complaints
  8. Institute of Acoustics and CIEH, Briefing Note: Heat Pumps (November 2022)

Google Reviews From Our Customers

Three First Point engineers in company hoodies in front of the liveried van, and a First Point engineer in a work hoodie in front of the company van, illustrating the team behind our Google reviews

More Guides

All Guides

Find The Right Spot Before Anything Gets Fixed

Four First Point engineers in black branded polos standing in a row in front of a dark grey crew van

At the free design survey our lead engineer measures the house and looks at where the outdoor unit can go, with siting checked against the sound calculation and the planning rules before anything goes on a wall.